Selectivity of circuit breakers

The circuit breakers used in the power distribution system can be divided into two categories: selective and non-selective according to their protection performance. Selective low-voltage circuit breaker with two-stage protection and three-stage protection. The instantaneous and short-delay characteristics are suitable for short-circuit operation, while the long-delay characteristics are suitable for overload protection.
Non-selective circuit breakers are generally instantaneous and only used for short-circuit protection. Some of them are long-delay actions and are only used for load protection. In the power distribution system, if the upper circuit breaker adopts a selective circuit breaker, and the next circuit breaker adopts a non-selective circuit breaker or a selective circuit breaker, it is mainly to use the difference in the delay action or delay action time of the short delay trip device to obtain selectivity. When delaying the operation of the upper circuit breaker, please pay attention to the following issues.
1) Regardless of whether the next stage is a selective circuit breaker or a non-selective circuit breaker, the setting current of the instantaneous overcurrent trip device of the upper circuit breaker shall generally not be less than 1.1 times of the maximum three-phase short-circuit current at the outlet end of the next level circuit breaker.
2) If the next stage is a non-selective circuit breaker, in order to prevent the short-circuit current from occurring in the circuit protected by the next level circuit breaker, the upper stage short-delay overcurrent tripper will act first because the instantaneous action sensitivity of this stage is not enough, so that it will lose its selectivity. Generally, the setting current of the short-delay overcurrent tripper of the upper circuit breaker is not less than 1.2 times that of the instantaneous overcurrent tripper of the next stage.
3) If the next stage is also a selective circuit breaker, in order to ensure selectivity, the short-delay action time of the higher-level circuit breaker is at least 0.1s longer than that of the next-level circuit breaker. Generally speaking, in order to ensure the selective action between the upper and lower low-voltage circuit breakers, the upper circuit breaker should choose an overcurrent tripper with a short delay, and its action current should be greater than the action current of the next level of overcurrent tripper, and at least the action current Iop.1 of the upper level is not less than 1.2 times of the action current Iop.2 of the next level, that is, Iop1≥1.2Iop.2.