As a leading supplier of 63 amp MCCBs (Molded Case Circuit Breakers), I often encounter inquiries from clients interested in connecting these powerful devices in parallel. Parallel connection of MCCBs is a technique used to increase the overall current - handling capacity of a circuit without having to use a single, larger - rated breaker. However, it's a process that requires careful consideration and strict adherence to electrical safety standards. In this blog, I'll walk you through the steps and considerations for safely connecting 63 amp MCCBs in parallel.
Understanding the Need for Parallel Connection
Before delving into the process, it's essential to understand why one might need to connect MCCBs in parallel. In some industrial or commercial applications, the electrical load may exceed the rating of a single 63 amp MCCB. Instead of installing a much larger and more expensive single breaker, parallel connection of multiple 63 amp MCCBs can be a cost - effective solution. For example, if you have a load that requires 126 amps of current, two 63 amp MCCBs connected in parallel can handle the load.


Prerequisites and Safety Precautions
- Matching Breakers: Ensure that all the 63 amp MCCBs you use are of the same model, manufacturer, and have identical trip characteristics. This is crucial because any differences in the trip settings can lead to uneven sharing of the load, potentially causing one breaker to trip prematurely while the others continue to carry current.
- Electrical System Analysis: Conduct a thorough electrical system analysis to determine the total available short - circuit current (SCC). This analysis will help you select the appropriate protective devices and ensure that the parallel - connected MCCBs can safely interrupt the fault current.
- Safety Gear: Always wear appropriate personal protective equipment (PPE), such as safety glasses, gloves, and flame - resistant clothing. Additionally, de - energize the circuit before starting any installation or maintenance work.
Step - by - Step Guide to Parallel Connection
Step 1: Planning the Layout
- First, carefully plan the physical layout of the MCCBs. They should be mounted in close proximity to each other on a suitable mounting panel. This helps in minimizing the differences in the impedance of the connection cables, which is essential for even current sharing.
- Ensure that there is sufficient space around the MCCBs for proper ventilation. Overheating can significantly affect the performance and lifespan of the breakers.
Step 2: Cable Selection
- Select high - quality cables with appropriate ampacity to carry the total current. The cable should be sized based on the combined rating of the parallel - connected MCCBs. For example, if you are connecting two 63 amp MCCBs, the cable should be rated for at least 126 amps.
- Use cables of the same length and cross - sectional area for each MCCB connection. This helps in equalizing the impedance of the parallel paths and ensures that the current is evenly distributed among the breakers.
Step 3: Making the Connections
- Incoming and Outgoing Connections: Connect the incoming supply cables to the line terminals of each MCCB. The connections should be tight and secure to prevent any loose connections that could lead to overheating. Similarly, connect the outgoing load cables to the load terminals of each MCCB.
- Neutral and Ground Connections: Ensure that the neutral and ground connections are made correctly. The neutral should be connected to the neutral terminals of each MCCB, and the ground should be connected to the grounding terminals to provide a safe path for fault current.
Step 4: Testing and Commissioning
- After making all the connections, perform a visual inspection to ensure that everything is correctly installed. Check for any loose wires, incorrect connections, or damaged components.
- Use a multimeter or a clamp - on ammeter to measure the current flowing through each MCCB. The current should be evenly distributed among the breakers. If there is a significant difference in the current readings, it may indicate an issue with the cable impedance or the breaker characteristics.
- Once the current distribution is verified, energize the circuit and monitor the MCCBs for a period of time to ensure that they are operating normally.
Common Mistakes to Avoid
- Uneven Cable Lengths: As mentioned earlier, using cables of different lengths can cause uneven current sharing. Always use cables of the same length and cross - sectional area.
- Incorrect Breaker Selection: Using MCCBs with different trip characteristics can lead to improper operation. Make sure all the breakers are of the same type and have identical trip settings.
- Overloading: Do not exceed the combined rating of the parallel - connected MCCBs. Overloading can cause the breakers to trip frequently and may damage the electrical system.
Additional Considerations
- Coordination with Other Protective Devices: Ensure that the parallel - connected MCCBs are coordinated with other protective devices in the circuit, such as Photovoltaic Direct Current Fuses and Step - up Transformers. This helps in providing selective protection and minimizing the impact of faults on the electrical system.
- Maintenance and Inspection: Regularly inspect and maintain the parallel - connected MCCBs. Check the connections for tightness, inspect the breaker contacts for signs of wear, and perform any necessary calibration or testing.
Applications and Use Cases
Parallel - connected 63 amp MCCBs find applications in a variety of industries. In the manufacturing industry, they can be used to power large motors or machinery where the current demand exceeds the capacity of a single breaker. In data centers, they can provide reliable power distribution to critical equipment. Additionally, they are also used in renewable energy systems, such as solar power plants, to handle high - current loads efficiently.
Conclusion
Connecting 63 amp MCCBs in parallel is a viable solution for increasing the current - handling capacity of an electrical circuit. However, it requires careful planning, proper installation, and strict adherence to safety standards. As a supplier of 63 amp MCCBs, we are committed to providing high - quality products and technical support to our clients. If you are considering parallel connection of MCCBs for your application, or if you have any questions about our products, we encourage you to reach out to us for a detailed discussion and procurement negotiation. We can help you select the right products and ensure a safe and efficient installation.
References
- Electrical Installation Guide, International Electrotechnical Commission (IEC)
- National Electrical Code (NEC), National Fire Protection Association (NFPA)
- MCCB Manufacturer's Technical Documentation






